NEC 705.12(B)(3)(2): when the solar breaker sits at the opposite end of the busbar from the main breaker, 125% of the inverter output current plus the main breaker rating may not exceed 120% of the busbar rating. On a 200 A busbar with a 200 A main that leaves 40 A, which is 32 A of inverter current, about a 7.6 kW inverter.
If the breaker can't go at the opposite end, the stricter 100% rule applies: the main breaker plus 125% of inverter current may not exceed the busbar rating.
When it doesn't fit, the usual fixes are a smaller main breaker (only if the load calculation allows it), a supply-side connection ahead of the main (705.11), or a panel with a larger busbar.
Inverter current from the database is estimated from rated power ÷ voltage. Use the maximum continuous output current printed on the datasheet when it differs.