How to size a solar string (NEC 690.7, step by step)

The two numbers that decide string length, the formulas behind them, and a worked example you can reproduce in the String Sizer.

A string is a set of panels wired in series into one inverter input. Series wiring adds voltages, so the string has to stay below the inverter's maximum DC voltage on the coldest morning and above its MPPT minimum on the hottest afternoon. Get the first wrong and you can damage the inverter; get the second wrong and you lose production on summer days.

Step 1: Find your record low temperature

Panel voltage rises as temperature falls. NEC 690.7 asks for the lowest expected ambient temperature, and the usual source is the ASHRAE extreme annual mean minimum design dry-bulb temperature for the nearest weather station. In the String Sizer, type your city and it fills this in. For Denver, CO the value is −23.6 °C.

Step 2: Correct the module's Voc for the cold

Use the datasheet's open-circuit voltage and its Voc temperature coefficient:

Voc_cold = Voc × [1 + β_Voc × (T_min − 25 °C)]
= 39.32 V × [1 + (-0.24%/°C) × (−23.6 − 25)] = 43.91 V

That is the Qcells Q.TRON BLK M-G2+ 430, which is 11.7% above its nameplate Voc on a Denver winter morning.

Step 3: Divide into the voltage limit

The limit is the lower of the inverter's max DC input and the module's max system voltage. For the Sol-Ark Limitless 15K-2P that is 500 V:

Max panels per string = ⌊ 500 V ÷ 43.91 V ⌋ = 11
400 V440 V480 V520 V560 V-30 °C-20 °C-10 °C0 °C10 °C20 °C30 °C40 °C Denver record low −23.6 °C 500 V inverter limit 12 panels 11 panels
String Voc against temperature. Eleven panels stay under 500 V even at Denver's record low; twelve cross the limit at about 0 °C, so a twelve-panel string would be over-voltage on any freezing morning.

Step 4: Check the hot side against the MPPT minimum

On a hot day the cells run far above air temperature. Tera Labs scales the datasheet NMOT rise to full sun (cell = air + (NMOT − 20) × 1.25), then lowers Vmp with its temperature coefficient. When a datasheet has no Vmp coefficient, it is estimated as the Pmax coefficient minus the Isc coefficient.

T_cell = 35 + (43 − 20) × 1.25 = 63.75 °C
Vmp_hot = 32.94 V × [1 + (-0.34%/°C) × (63.75 − 25)] = 28.60 V
Min panels = ⌈ 150 V ÷ 28.60 V ⌉ = 6

So with this pairing in Denver, any string from 6 to 11 panels works. Below 175 V the Sol-Ark is outside its full-power MPPT range, so the String Sizer flags short strings as "works, derates".

Step 5: Check current per MPPT

Each MPPT has a short-circuit current limit. The hot-day Isc here is 13.95 A per string, and the Sol-Ark accepts 44 A per MPPT with 2 inputs, so 2 strings fit on each MPPT. Some designers also apply the NEC 690.8 125% factor; the String Sizer has a switch for that.

Result: up to 11 × 430 W panels per string, 2 strings per MPPT. Open this example in the String Sizer →

Microinverters and SolarEdge work differently

Microinverters take one or two modules each, so there is no string to size. The check is whether one module fits the input window: max input voltage on the coldest day, MPPT range on hot and cold days, current, and the recommended module power. The limit becomes how many units fit on a 20 A branch circuit.

SolarEdge optimizers hold the string at a fixed voltage, so length is set by optimizer count (for example 8–25 S440s on single-phase inverters) and power per string (5,700 W usable). The module still has to fit the optimizer's input limits.

Common mistakes

  • Using the average January low instead of the design record low.
  • Forgetting that the module's own max system voltage (often 1000 V) can be lower than the inverter's limit on commercial jobs.
  • Ignoring bifacial rear gain when checking current limits.
  • Putting strings of different lengths on the same MPPT.

This guide is for education. Confirm every design with the inverter manufacturer's sizing tool, current datasheets and your authority having jurisdiction.