Home › Calculators › 120% rule

120% rule calculator

Can this main panel take the solar breaker? Enter the busbar and main breaker ratings and the inverter output current, or pick an inverter from the database.

How it works

NEC 705.12(B)(3)(2): when the solar breaker sits at the opposite end of the busbar from the main breaker, 125% of the inverter output current plus the main breaker rating may not exceed 120% of the busbar rating. On a 200 A busbar with a 200 A main that leaves 40 A, which is 32 A of inverter current, about a 7.6 kW inverter.

If the breaker can't go at the opposite end, the stricter 100% rule applies: the main breaker plus 125% of inverter current may not exceed the busbar rating.

When it doesn't fit, the usual fixes are a smaller main breaker (only if the load calculation allows it), a supply-side connection ahead of the main (705.11), or a panel with a larger busbar.

Inverter current from the database is estimated from rated power ÷ voltage. Use the maximum continuous output current printed on the datasheet when it differs.

Questions

What is the 120% rule for solar?

It limits how much solar can backfeed a panel through a breaker: main breaker + 125% of inverter current ≤ 120% of busbar rating, with the solar breaker at the opposite end of the busbar.

How much solar can a 200 A panel take?

With a 200 A busbar and a 200 A main, 40 A of breaker capacity: 32 A of continuous inverter current, roughly 7.6 kW at 240 V. Downsizing the main to 175 A raises that to 52 A of current.

Estimates only, based on NEC 2020/2023 tables. Check the code edition your jurisdiction uses, the equipment datasheets and your AHJ before you build.