Home › Compatibility › Canadian Solar HiKu6 CS6R-410MS + EG4 6000XP

Canadian Solar HiKu6 CS6R-410MS with EG4 6000XP

Compatibility and string sizing for this panel and hybrid inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 5–11 panels work. The longest string reaches 446 V on the coldest morning, under the 480 V inverter limit.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C5–11 panels per string (best 10)
Chicago, IL−21 °C5–11 panels per string (best 10)
Denver, CO−23.6 °C5–11 panels per string (best 10)
Atlanta, GA−9.5 °C5–11 panels per string (best 10)
Dallas, TX−7.1 °C5–11 panels per string (best 10)
Phoenix, AZ1.3 °C5–12 panels per string (best 11)
Miami, FL5.9 °C5–12 panels per string (best 11)

Common system sizes

How Canadian Solar HiKu6 CS6R-410MS panels lay out on the EG4 6000XP for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW151 × 8 + 1 × 7 panels on 1 inverter6.15 kWp1.03
About 8 kW202 × 7 + 1 × 6 panels on 2 inverters8.20 kWp0.68
About 10 kW243 strings of 8 on 2 inverters9.84 kWp0.82