Home › Compatibility › Canadian Solar HiKu6 CS6R-410MS + Hoymiles HMS-700-2T-NA

Canadian Solar HiKu6 CS6R-410MS with Hoymiles HMS-700-2T-NA

Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.

!

Compatible, with a caution

Yes. Each HMS-700-2T-NA takes 2 panels, and up to 6 units fit on one 20 A branch circuit (12 panels). DC/AC ratio 1.29. Check the Input current below.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C2 panels per unit (check: Input current)
Chicago, IL−21 °C2 panels per unit (check: Input current)
Denver, CO−23.6 °C2 panels per unit (check: Input current)
Atlanta, GA−9.5 °C2 panels per unit (check: Input current)
Dallas, TX−7.1 °C2 panels per unit (check: Input current)
Phoenix, AZ1.3 °C2 panels per unit (check: Input current)
Miami, FL5.9 °C2 panels per unit (check: Input current)

Common system sizes

How Canadian Solar HiKu6 CS6R-410MS panels lay out on the Hoymiles HMS-700-2T-NA for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW158 × HMS-700-2T-NA on 2 branch circuits6.15 kWp1.20
About 8 kW2010 × HMS-700-2T-NA on 2 branch circuits8.20 kWp1.29
About 10 kW2412 × HMS-700-2T-NA on 2 branch circuits9.84 kWp1.29