Home › Compatibility › Canadian Solar HiKu6 CS6R-410MS + SMA STP 50-US-41

Canadian Solar HiKu6 CS6R-410MS with SMA STP 50-US-41

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 6–24 panels work. The longest string reaches 974 V on the coldest morning, under the 1000 V inverter limit. One SMA STP 50-US-41 takes up to 7 strings of 24: 168 panels, 68.88 kWp DC, DC/AC ratio 1.38.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C6–23 panels per string (best 23)
Chicago, IL−21 °C6–24 panels per string (best 24)
Denver, CO−23.6 °C6–23 panels per string (best 23)
Atlanta, GA−9.5 °C6–24 panels per string (best 24)
Dallas, TX−7.1 °C6–24 panels per string (best 24)
Phoenix, AZ1.3 °C6–25 panels per string (best 25)
Miami, FL5.9 °C6–25 panels per string (best 25)

Common system sizes

How Canadian Solar HiKu6 CS6R-410MS panels lay out on the SMA STP 50-US-41 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded18012 strings of 15 on 1 inverter73.80 kWp1.48
2 inverters, fully loaded36024 strings of 15 on 2 inverters147.60 kWp1.48
4 inverters, fully loaded72048 strings of 15 on 4 inverters295.20 kWp1.48