Canadian Solar HiKu6 CS6R-410MS with Solis S5-GC75K-US
Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.
Compatible
Yes. At a −10 °C record low and a 40 °C hot day, strings of 7–24 panels work. The longest string reaches 974 V on the coldest morning, under the 1000 V inverter limit. One Solis S5-GC75K-US takes up to 16 strings of 24: 384 panels, 157.44 kWp DC, DC/AC ratio 2.10.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- Voc on the coldest morning37.2 V × (1 + -0.26%/°C × (−10 − 25)) = 40.59 V per panel.
- Vmp on the hottest afternoonCells reach 66.2 °C (40 °C air plus the NMOT rise), so Vmp drops from 31.2 V to 26.18 V (Vmp coefficient taken as Pmax − Isc coefficient).
- Longest string1000 V inverter limit ÷ 40.59 V = 24 panels.
- Shortest string180 V MPPT minimum ÷ 26.18 V = 7 panels; start-up voltage needs 6.
- Strings per MPPTHot-day Isc 14.30 A per string, so the MPPT inputs take 2 + 2 + 2 + 2 + 2 + 2 + 2 + 2 string(s).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 7–23 panels per string (best 23) |
| Chicago, IL | −21 °C | 7–24 panels per string (best 24) |
| Denver, CO | −23.6 °C | 7–23 panels per string (best 23) |
| Atlanta, GA | −9.5 °C | 7–24 panels per string (best 24) |
| Dallas, TX | −7.1 °C | 7–24 panels per string (best 24) |
| Phoenix, AZ | 1.3 °C | 7–25 panels per string (best 25) |
| Miami, FL | 5.9 °C | 7–25 panels per string (best 25) |
Common system sizes
How Canadian Solar HiKu6 CS6R-410MS panels lay out on the Solis S5-GC75K-US for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| 1 inverter, fully loaded | 384 | 16 strings of 24 on 1 inverter | 157.44 kWp | 2.10 |
| 2 inverters, fully loaded | 768 | 32 strings of 24 on 2 inverters | 314.88 kWp | 2.10 |
| 4 inverters, fully loaded | 1536 | 64 strings of 24 on 4 inverters | 629.76 kWp | 2.10 |