Home › Compatibility › Canadian Solar CS6R-410MS-HL + SolarEdge SE3800H-US
Canadian Solar CS6R-410MS-HL with SolarEdge SE3800H-US
Compatibility and string sizing for this panel and solaredge inverter, calculated from both datasheets.
✓
Compatible
Yes, with the SolarEdge S440 optimizer on every panel. Strings of 8–14 panels work (best 13), each delivering up to 5,700 W.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- ✓ Module power410 W is within the S440 rating of 440 W.
- ✓ Max input voltageVoc at the record low is 40.6 V, within the 60 V optimizer limit.
- ✓ MPPT windowVmp stays inside 8–60 V from the coldest to the hottest day.
- ✓ Module short-circuit currentIsc 14.01 A is within the 15 A limit.
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 8–14 panels per string (best 13) |
| Chicago, IL | −21 °C | 8–14 panels per string (best 13) |
| Denver, CO | −23.6 °C | 8–14 panels per string (best 13) |
| Atlanta, GA | −9.5 °C | 8–14 panels per string (best 13) |
| Dallas, TX | −7.1 °C | 8–14 panels per string (best 13) |
| Phoenix, AZ | 1.3 °C | 8–14 panels per string (best 13) |
| Miami, FL | 5.9 °C | 8–14 panels per string (best 13) |
Common system sizes
How Canadian Solar CS6R-410MS-HL panels lay out on the SolarEdge SE3800H-US for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | Each string needs at least 8 optimizers, but this split gives only 7 panels per string. Add panels or use fewer strings. | |||
| About 8 kW | 20 | 2 strings of 10 on 2 inverters | 8.20 kWp | 1.08 |
| About 10 kW | 24 | 2 strings of 12 on 2 inverters | 9.84 kWp | 1.29 |