Home › Compatibility › Canadian Solar TOPBiHiKu6 CS6.2-66TB-620 + Hoymiles HMS-1600-4T-NA
Canadian Solar TOPBiHiKu6 CS6.2-66TB-620 with Hoymiles HMS-1600-4T-NA
Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.
!
Compatible, with a caution
Yes. Each HMS-1600-4T-NA takes 4 panels, and up to 2 units fit on one 20 A branch circuit (8 panels). DC/AC ratio 1.72. Check the Input current; Module power pairing below.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.
- ✓ Max input voltageVoc at the record low is 52.6 V, within the 65 V limit (81%).
- ✓ MPPT window, hot dayVmp on the hottest day is 35.4 V, inside 16–60 V.
- ✓ MPPT window, cold dayVmp on the coldest day is 46.1 V, inside the MPPT range.
- ✓ Start-up voltageHot-day Voc 43.4 V clears the 22 V start-up voltage.
- ! Input currentImp 16.57 A is above the 14 A max input current, so some clipping. The datasheet gives no separate Isc limit.
- ! Module power pairing620 W is above the recommended 320–540 W, so expect midday clipping (DC/AC 1.72).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 4 panels per unit (check: Input current) |
| Chicago, IL | −21 °C | 4 panels per unit (check: Input current) |
| Denver, CO | −23.6 °C | 4 panels per unit (check: Input current) |
| Atlanta, GA | −9.5 °C | 4 panels per unit (check: Input current) |
| Dallas, TX | −7.1 °C | 4 panels per unit (check: Input current) |
| Phoenix, AZ | 1.3 °C | 4 panels per unit (check: Input current) |
| Miami, FL | 5.9 °C | 4 panels per unit (check: Input current) |
Common system sizes
How Canadian Solar TOPBiHiKu6 CS6.2-66TB-620 panels lay out on the Hoymiles HMS-1600-4T-NA for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | 10 | 3 × HMS-1600-4T-NA on 2 branch circuits | 6.20 kWp | 1.44 |
| About 8 kW | 13 | 4 × HMS-1600-4T-NA on 2 branch circuits | 8.06 kWp | 1.40 |
| About 10 kW | 16 | 4 × HMS-1600-4T-NA on 2 branch circuits | 9.92 kWp | 1.72 |