Home › Compatibility › Canadian Solar TOPBiHiKu6 CS6.2-66TB-620 + SMA STP 33-US-41

Canadian Solar TOPBiHiKu6 CS6.2-66TB-620 with SMA STP 33-US-41

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 5–18 panels work. The longest string reaches 947 V on the coldest morning, under the 1000 V inverter limit. One SMA STP 33-US-41 takes up to 4 strings of 18: 72 panels, 44.64 kWp DC, DC/AC ratio 1.34.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C5–18 panels per string (best 18)
Chicago, IL−21 °C5–18 panels per string (best 18)
Denver, CO−23.6 °C5–18 panels per string (best 18)
Atlanta, GA−9.5 °C5–19 panels per string (best 19)
Dallas, TX−7.1 °C5–19 panels per string (best 19)
Phoenix, AZ1.3 °C5–19 panels per string (best 19)
Miami, FL5.9 °C5–19 panels per string (best 19)

Common system sizes

How Canadian Solar TOPBiHiKu6 CS6.2-66TB-620 panels lay out on the SMA STP 33-US-41 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded805 strings of 16 on 1 inverter49.60 kWp1.49
2 inverters, fully loaded16010 strings of 16 on 2 inverters99.20 kWp1.49
4 inverters, fully loaded32020 strings of 16 on 4 inverters198.40 kWp1.49