Home › Compatibility › Canadian Solar TOPBiHiKu6 CS6.2-66TB-620 + Sol-Ark 8K-2P-N

Canadian Solar TOPBiHiKu6 CS6.2-66TB-620 with Sol-Ark 8K-2P-N

Compatibility and string sizing for this panel and hybrid inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 5–9 panels work. The longest string reaches 474 V on the coldest morning, under the 500 V inverter limit. One Sol-Ark 8K-2P-N takes up to 1 string of 9: 9 panels, 5.58 kWp DC, DC/AC ratio 0.70.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C5–9 panels per string (best 9)
Chicago, IL−21 °C5–9 panels per string (best 9)
Denver, CO−23.6 °C5–9 panels per string (best 9)
Atlanta, GA−9.5 °C5–9 panels per string (best 9)
Dallas, TX−7.1 °C5–9 panels per string (best 9)
Phoenix, AZ1.3 °C5–9 panels per string (best 9)
Miami, FL5.9 °C5–9 panels per string (best 9)

Common system sizes

How Canadian Solar TOPBiHiKu6 CS6.2-66TB-620 panels lay out on the Sol-Ark 8K-2P-N for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW102 strings of 5 on 1 inverter6.20 kWp0.78
About 8 kW131 × 7 + 1 × 6 panels on 1 inverter8.06 kWp1.01
About 10 kW162 strings of 8 on 1 inverter9.92 kWp1.24