Canadian Solar TOPBiHiKu6 CS6.2-66TB-620 with Solis S6-GC36K-US
Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.
Compatible
Yes. At a −10 °C record low and a 40 °C hot day, strings of 6–18 panels work. The longest string reaches 947 V on the coldest morning, under the 1000 V inverter limit. One Solis S6-GC36K-US takes up to 6 strings of 18: 108 panels, 66.96 kWp DC, DC/AC ratio 1.86.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.
- Voc on the coldest morning48.4 V × (1 + -0.25%/°C × (−10 − 25)) = 52.63 V per panel.
- Vmp on the hottest afternoonCells reach 66.2 °C (40 °C air plus the NMOT rise), so Vmp drops from 41.2 V to 35.42 V (Vmp coefficient taken as Pmax − Isc coefficient).
- Longest string1000 V inverter limit ÷ 52.63 V = 18 panels.
- Shortest string180 V MPPT minimum ÷ 35.42 V = 6 panels; start-up voltage needs 5.
- Strings per MPPTHot-day Isc 18.05 A per string, so the MPPT inputs take 2 + 2 + 2 string(s).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 6–18 panels per string (best 18) |
| Chicago, IL | −21 °C | 6–18 panels per string (best 18) |
| Denver, CO | −23.6 °C | 6–18 panels per string (best 18) |
| Atlanta, GA | −9.5 °C | 6–19 panels per string (best 19) |
| Dallas, TX | −7.1 °C | 6–19 panels per string (best 19) |
| Phoenix, AZ | 1.3 °C | 6–19 panels per string (best 19) |
| Miami, FL | 5.9 °C | 6–19 panels per string (best 19) |
Common system sizes
How Canadian Solar TOPBiHiKu6 CS6.2-66TB-620 panels lay out on the Solis S6-GC36K-US for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| 1 inverter, fully loaded | 108 | 6 strings of 18 on 1 inverter | 66.96 kWp | 1.86 |
| 2 inverters, fully loaded | 216 | 12 strings of 18 on 2 inverters | 133.92 kWp | 1.86 |
| 4 inverters, fully loaded | 432 | 24 strings of 18 on 4 inverters | 267.84 kWp | 1.86 |