Home › Compatibility › JA Solar JAM54D41-435/MB + Hoymiles HMS-2000-4T-NA

JA Solar JAM54D41-435/MB with Hoymiles HMS-2000-4T-NA

Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.

✓

Compatible

Yes. Each HMS-2000-4T-NA takes 4 panels, and up to 2 units fit on one 20 A branch circuit (8 panels). DC/AC ratio 0.91.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C4 panels per unit
Chicago, IL−21 °C4 panels per unit
Denver, CO−23.6 °C4 panels per unit
Atlanta, GA−9.5 °C4 panels per unit
Dallas, TX−7.1 °C4 panels per unit
Phoenix, AZ1.3 °C4 panels per unit
Miami, FL5.9 °C4 panels per unit

Common system sizes

How JA Solar JAM54D41-435/MB panels lay out on the Hoymiles HMS-2000-4T-NA for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW144 × HMS-2000-4T-NA on 2 branch circuits6.09 kWp0.79
About 8 kW185 × HMS-2000-4T-NA on 3 branch circuits7.83 kWp0.82
About 10 kW236 × HMS-2000-4T-NA on 3 branch circuits10.01 kWp0.87