Home › Compatibility › Jinko Solar JKM450M-7RL3 + APsystems DS3-S

Jinko Solar JKM450M-7RL3 with APsystems DS3-S

Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.

!

Compatible, with a caution

Yes. Each DS3-S takes 2 panels, and up to 6 units fit on one 20 A branch circuit (12 panels). DC/AC ratio 1.41. Check the MPPT window, cold day below.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C2 panels per unit (check: MPPT window, cold day)
Chicago, IL−21 °C2 panels per unit (check: MPPT window, cold day)
Denver, CO−23.6 °C2 panels per unit (check: MPPT window, cold day)
Atlanta, GA−9.5 °C2 panels per unit (check: MPPT window, cold day)
Dallas, TX−7.1 °C2 panels per unit (check: MPPT window, cold day)
Phoenix, AZ1.3 °C2 panels per unit
Miami, FL5.9 °C2 panels per unit

Common system sizes

How Jinko Solar JKM450M-7RL3 panels lay out on the APsystems DS3-S for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW137 × DS3-S on 2 branch circuits5.85 kWp1.31
About 8 kW189 × DS3-S on 2 branch circuits8.10 kWp1.41
About 10 kW2211 × DS3-S on 2 branch circuits9.90 kWp1.41