Home › Compatibility › Jinko Solar JKM450M-7RL3 + APsystems DS3
Jinko Solar JKM450M-7RL3 with APsystems DS3
Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.
✓
Compatible
Yes. Each DS3 takes 2 panels, and up to 4 units fit on one 20 A branch circuit (8 panels). DC/AC ratio 1.02.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- ✓ Max input voltageVoc at the record low is 57.1 V, within the 60 V limit (95%).
- ✓ MPPT window, hot dayVmp on the hottest day is 34.4 V, inside 32–55 V.
- ✓ MPPT window, cold dayVmp on the coldest day is 49.2 V, inside the MPPT range.
- ✓ Input currentImp 10.50 A is within the 20 A max input current. The datasheet gives no separate Isc limit.
- ✓ Module power pairing450 W is inside the recommended 300–660 (DC/AC 1.02).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 2 panels per unit |
| Chicago, IL | −21 °C | 2 panels per unit |
| Denver, CO | −23.6 °C | 2 panels per unit |
| Atlanta, GA | −9.5 °C | 2 panels per unit |
| Dallas, TX | −7.1 °C | 2 panels per unit |
| Phoenix, AZ | 1.3 °C | 2 panels per unit |
| Miami, FL | 5.9 °C | 2 panels per unit |
Common system sizes
How Jinko Solar JKM450M-7RL3 panels lay out on the APsystems DS3 for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | 13 | 7 × DS3 on 2 branch circuits | 5.85 kWp | 0.95 |
| About 8 kW | 18 | 9 × DS3 on 3 branch circuits | 8.10 kWp | 1.02 |
| About 10 kW | 22 | 11 × DS3 on 3 branch circuits | 9.90 kWp | 1.02 |