Home › Compatibility › Jinko Solar Tiger Neo JKM580N-72HL4-BDV + SMA STP 50-US-41

Jinko Solar Tiger Neo JKM580N-72HL4-BDV with SMA STP 50-US-41

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 5–17 panels work. The longest string reaches 952 V on the coldest morning, under the 1000 V inverter limit. One SMA STP 50-US-41 takes up to 6 strings of 17: 102 panels, 59.16 kWp DC, DC/AC ratio 1.18.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C5–17 panels per string (best 17)
Chicago, IL−21 °C5–17 panels per string (best 17)
Denver, CO−23.6 °C5–17 panels per string (best 17)
Atlanta, GA−9.5 °C5–17 panels per string (best 17)
Dallas, TX−7.1 °C5–17 panels per string (best 17)
Phoenix, AZ1.3 °C5–18 panels per string (best 18)
Miami, FL5.9 °C5–18 panels per string (best 18)

Common system sizes

How Jinko Solar Tiger Neo JKM580N-72HL4-BDV panels lay out on the SMA STP 50-US-41 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded1026 strings of 17 on 1 inverter59.16 kWp1.18
2 inverters, fully loaded20412 strings of 17 on 2 inverters118.32 kWp1.18
4 inverters, fully loaded40824 strings of 17 on 4 inverters236.64 kWp1.18