Jinko Solar Tiger Neo JKM590N-72HL4-BDV with EG4 FlexBOSS21
Compatibility and string sizing for this panel and hybrid inverter, calculated from both datasheets.
Compatible
Yes. At a −10 °C record low and a 40 °C hot day, strings of 5–10 panels work. The longest string reaches 564 V on the coldest morning, under the 600 V inverter limit. One EG4 FlexBOSS21 takes up to 3 strings of 9: 27 panels, 15.93 kWp DC, DC/AC ratio 1.00.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.
- Voc on the coldest morning51.86 V × (1 + -0.25%/°C × (−10 − 25)) = 56.40 V per panel.
- Vmp on the hottest afternoonCells reach 71.2 °C (40 °C air plus the NMOT rise), so Vmp drops from 42.88 V to 36.24 V (Vmp coefficient taken as Pmax − Isc coefficient).
- Longest string600 V inverter limit ÷ 56.40 V = 10 panels.
- Shortest string120 V MPPT minimum ÷ 36.24 V = 4 panels; start-up voltage needs 5.
- Strings per MPPTHot-day Isc 16.27 A per string, so the MPPT inputs take 1 + 1 + 1 string(s); expect about 0.9% current clipping at peak.
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 5–10 panels per string (best 8) |
| Chicago, IL | −21 °C | 5–10 panels per string (best 8) |
| Denver, CO | −23.6 °C | 5–10 panels per string (best 8) |
| Atlanta, GA | −9.5 °C | 5–10 panels per string (best 9) |
| Dallas, TX | −7.1 °C | 5–10 panels per string (best 9) |
| Phoenix, AZ | 1.3 °C | 5–10 panels per string (best 9) |
| Miami, FL | 5.9 °C | 5–11 panels per string (best 9) |
Common system sizes
How Jinko Solar Tiger Neo JKM590N-72HL4-BDV panels lay out on the EG4 FlexBOSS21 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| 1 inverter, fully loaded | 30 | 3 strings of 10 on 1 inverter | 17.70 kWp | 1.11 |
| 2 inverters, fully loaded | 60 | 6 strings of 10 on 2 inverters | 35.40 kWp | 1.11 |
| 4 inverters, fully loaded | 120 | 12 strings of 10 on 4 inverters | 70.80 kWp | 1.11 |