Home › Compatibility › Jinko Solar Tiger Neo JKM590N-72HL4-BDV + Enphase IQ8M-72-2-US
Jinko Solar Tiger Neo JKM590N-72HL4-BDV with Enphase IQ8M-72-2-US
Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.
!
Compatible, with a caution
Yes. Each IQ8M-72-2-US takes 1 panel, and up to 11 units fit on one 20 A branch circuit (11 panels). DC/AC ratio 1.82. Check the MPPT window, cold day; Module power pairing below.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.
- ✓ Max input voltageVoc at the record low is 56.4 V, within the 60 V limit (94%).
- ✓ MPPT window, hot dayVmp on the hottest day is 36.2 V, inside 30–45 V.
- ! MPPT window, cold dayVmp rises to 47.9 V on cold days, above the 45 V MPPT maximum, so tracking is off-peak then.
- ✓ Start-up voltageHot-day Voc 45.9 V clears the 22 V start-up voltage.
- ✓ Module short-circuit currentIsc 15.94 A incl. bifacial gain is within the 20 A max module Isc.
- ! Module power pairing590 W is above the recommended 260–460 W, so expect midday clipping (DC/AC 1.82).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 1 panel per unit (check: MPPT window, cold day) |
| Chicago, IL | −21 °C | 1 panel per unit (check: MPPT window, cold day) |
| Denver, CO | −23.6 °C | 1 panel per unit (check: MPPT window, cold day) |
| Atlanta, GA | −9.5 °C | 1 panel per unit (check: MPPT window, cold day) |
| Dallas, TX | −7.1 °C | 1 panel per unit (check: MPPT window, cold day) |
| Phoenix, AZ | 1.3 °C | 1 panel per unit (check: MPPT window, cold day) |
| Miami, FL | 5.9 °C | 1 panel per unit (check: MPPT window, cold day) |
Common system sizes
How Jinko Solar Tiger Neo JKM590N-72HL4-BDV panels lay out on the Enphase IQ8M-72-2-US for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | 10 | 10 × IQ8M-72-2-US on 1 branch circuit | 5.90 kWp | 1.82 |
| About 8 kW | 14 | 14 × IQ8M-72-2-US on 2 branch circuits | 8.26 kWp | 1.82 |
| About 10 kW | 17 | 17 × IQ8M-72-2-US on 2 branch circuits | 10.03 kWp | 1.82 |