LONGi Hi-MO 6 LR5-54HTB-435M with SMA SB7.7-1SP-US-41

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 4–14 panels work. The longest string reaches 599 V on the coldest morning, under the 600 V inverter limit. One SMA SB7.7-1SP-US-41 takes up to 2 strings of 14: 28 panels, 12.18 kWp DC, DC/AC ratio 1.59.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C4–13 panels per string (best 13)
Chicago, IL−21 °C4–13 panels per string (best 13)
Denver, CO−23.6 °C4–13 panels per string (best 13)
Atlanta, GA−9.5 °C4–14 panels per string (best 14)
Dallas, TX−7.1 °C4–14 panels per string (best 14)
Phoenix, AZ1.3 °C4–14 panels per string (best 14)
Miami, FL5.9 °C4–14 panels per string (best 14)

Common system sizes

How LONGi Hi-MO 6 LR5-54HTB-435M panels lay out on the SMA SB7.7-1SP-US-41 for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW141 string of 14 on 1 inverter6.09 kWp0.79
About 8 kW182 strings of 9 on 1 inverter7.83 kWp1.02
About 10 kW231 × 12 + 1 × 11 panels on 1 inverter10.01 kWp1.30