Maxeon SPR-MAX3-430 with SolarEdge SE11400H-US
Compatibility and string sizing for this panel and solaredge inverter, calculated from both datasheets.
Compatible
Yes, with the SolarEdge S500B optimizer on every panel. Strings of 6–15 panels work (best 13), each delivering up to 5,700 W. One SolarEdge SE11400H-US takes up to 3 strings of 13: 39 panels, 16.77 kWp DC, DC/AC ratio 1.47.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- ✓ Module power430 W is within the S500B rating of 650 W.
- ✓ Max input voltageVoc at the record low is 88.0 V, within the 125 V optimizer limit.
- ✓ MPPT windowVmp stays inside 12.5–105 V from the coldest to the hottest day.
- ✓ Module short-circuit currentIsc 6.57 A is within the 15 A limit.
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 6–15 panels per string (best 13) |
| Chicago, IL | −21 °C | 6–15 panels per string (best 13) |
| Denver, CO | −23.6 °C | 6–15 panels per string (best 13) |
| Atlanta, GA | −9.5 °C | 6–15 panels per string (best 13) |
| Dallas, TX | −7.1 °C | 6–15 panels per string (best 13) |
| Phoenix, AZ | 1.3 °C | 6–15 panels per string (best 13) |
| Miami, FL | 5.9 °C | 6–15 panels per string (best 13) |
Common system sizes
How Maxeon SPR-MAX3-430 panels lay out on the SolarEdge SE11400H-US for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | 14 | 1 string of 14 on 1 inverter | 6.02 kWp | 0.53 |
| About 8 kW | 19 | 1 × 10 + 1 × 9 panels on 1 inverter | 8.17 kWp | 0.72 |
| About 10 kW | 23 | 1 × 12 + 1 × 11 panels on 1 inverter | 9.89 kWp | 0.87 |