Home › Compatibility › Meyer Burger Meyer Burger White 400W + Enphase IQ8HC-72-M-US
Meyer Burger Meyer Burger White 400W with Enphase IQ8HC-72-M-US
Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.
✓
Compatible
Yes. Each IQ8HC-72-M-US takes 1 panel, and up to 10 units fit on one 20 A branch circuit (10 panels). DC/AC ratio 1.05.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- ✓ Max input voltageVoc at the record low is 48.3 V, within the 60 V limit (81%).
- ✓ MPPT window, hot dayVmp on the hottest day is 33.0 V, inside 29.5–45 V.
- ✓ MPPT window, cold dayVmp on the coldest day is 42.0 V, inside the MPPT range.
- ✓ Start-up voltageHot-day Voc 39.7 V clears the 22 V start-up voltage.
- ✓ Module short-circuit currentIsc 11.10 A is within the 20 A max module Isc.
- ✓ Module power pairing400 W is inside the recommended 320–540 (DC/AC 1.05).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 1 panel per unit |
| Chicago, IL | −21 °C | 1 panel per unit |
| Denver, CO | −23.6 °C | 1 panel per unit |
| Atlanta, GA | −9.5 °C | 1 panel per unit |
| Dallas, TX | −7.1 °C | 1 panel per unit |
| Phoenix, AZ | 1.3 °C | 1 panel per unit |
| Miami, FL | 5.9 °C | 1 panel per unit |
Common system sizes
How Meyer Burger Meyer Burger White 400W panels lay out on the Enphase IQ8HC-72-M-US for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | 15 | 15 × IQ8HC-72-M-US on 2 branch circuits | 6.00 kWp | 1.05 |
| About 8 kW | 20 | 20 × IQ8HC-72-M-US on 2 branch circuits | 8.00 kWp | 1.05 |
| About 10 kW | 25 | 25 × IQ8HC-72-M-US on 3 branch circuits | 10.00 kWp | 1.05 |