Home › Compatibility › Mission Solar MSX10-435HN0B + CPS (Chint Power) SCA25KTL-DO/US-208

Mission Solar MSX10-435HN0B with CPS (Chint Power) SCA25KTL-DO/US-208

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 10–23 panels work. The longest string reaches 989 V on the coldest morning, under the 1000 V inverter limit. One CPS (Chint Power) SCA25KTL-DO/US-208 takes up to 3 strings of 23: 69 panels, 30.02 kWp DC, DC/AC ratio 1.20.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C10–22 panels per string (best 22)
Chicago, IL−21 °C10–22 panels per string (best 22)
Denver, CO−23.6 °C10–22 panels per string (best 22)
Atlanta, GA−9.5 °C10–23 panels per string (best 23)
Dallas, TX−7.1 °C10–23 panels per string (best 23)
Phoenix, AZ1.3 °C10–23 panels per string (best 23)
Miami, FL5.9 °C10–24 panels per string (best 24)

Common system sizes

How Mission Solar MSX10-435HN0B panels lay out on the CPS (Chint Power) SCA25KTL-DO/US-208 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded1026 strings of 17 on 1 inverter44.37 kWp1.77
2 inverters, fully loaded20412 strings of 17 on 2 inverters88.74 kWp1.77
4 inverters, fully loaded40824 strings of 17 on 4 inverters177.48 kWp1.77