Mission Solar MSX10-435HN0B with Fronius Symo 22.7-3 480

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 8–23 panels work. The longest string reaches 989 V on the coldest morning, under the 1000 V inverter limit. One Fronius Symo 22.7-3 480 takes up to 3 strings of 21: 63 panels, 27.41 kWp DC, DC/AC ratio 1.21.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C8–22 panels per string (best 20)
Chicago, IL−21 °C8–22 panels per string (best 20)
Denver, CO−23.6 °C8–22 panels per string (best 20)
Atlanta, GA−9.5 °C8–23 panels per string (best 21)
Dallas, TX−7.1 °C8–23 panels per string (best 21)
Phoenix, AZ1.3 °C8–23 panels per string (best 22)
Miami, FL5.9 °C8–24 panels per string (best 22)

Common system sizes

How Mission Solar MSX10-435HN0B panels lay out on the Fronius Symo 22.7-3 480 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded663 strings of 22 on 1 inverter28.71 kWp1.26
2 inverters, fully loaded1326 strings of 22 on 2 inverters57.42 kWp1.26
4 inverters, fully loaded26412 strings of 22 on 4 inverters114.84 kWp1.26