Home › Compatibility › Mission Solar MSX10-435HN0B + Sol-Ark 60K-3P-480V

Mission Solar MSX10-435HN0B with Sol-Ark 60K-3P-480V

Compatibility and string sizing for this panel and hybrid inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 6–23 panels work. The longest string reaches 989 V on the coldest morning, under the 1000 V inverter limit. One Sol-Ark 60K-3P-480V takes up to 8 strings of 22: 176 panels, 76.56 kWp DC, DC/AC ratio 1.28.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C6–22 panels per string (best 21)
Chicago, IL−21 °C6–22 panels per string (best 22)
Denver, CO−23.6 °C6–22 panels per string (best 21)
Atlanta, GA−9.5 °C6–23 panels per string (best 22)
Dallas, TX−7.1 °C6–23 panels per string (best 23)
Phoenix, AZ1.3 °C6–23 panels per string (best 23)
Miami, FL5.9 °C6–24 panels per string (best 23)

Common system sizes

How Mission Solar MSX10-435HN0B panels lay out on the Sol-Ark 60K-3P-480V for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded1768 strings of 22 on 1 inverter76.56 kWp1.28
2 inverters, fully loaded35216 strings of 22 on 2 inverters153.12 kWp1.28
4 inverters, fully loaded70432 strings of 22 on 4 inverters306.24 kWp1.28