Home › Compatibility › Mission Solar MSX10-445HN0B + Sol-Ark 12K-2P-LL

Mission Solar MSX10-445HN0B with Sol-Ark 12K-2P-LL

Compatibility and string sizing for this panel and hybrid inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 6–11 panels work. The longest string reaches 479 V on the coldest morning, under the 500 V inverter limit. One Sol-Ark 12K-2P-LL takes up to 4 strings of 10: 40 panels, 17.80 kWp DC, DC/AC ratio 1.48.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C6–10 panels per string (best 10)
Chicago, IL−21 °C6–11 panels per string (best 10)
Denver, CO−23.6 °C6–11 panels per string (best 10)
Atlanta, GA−9.5 °C6–11 panels per string (best 10)
Dallas, TX−7.1 °C6–11 panels per string (best 11)
Phoenix, AZ1.3 °C6–11 panels per string (best 11)
Miami, FL5.9 °C6–11 panels per string (best 11)

Common system sizes

How Mission Solar MSX10-445HN0B panels lay out on the Sol-Ark 12K-2P-LL for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW131 × 7 + 1 × 6 panels on 1 inverter5.79 kWp0.48
About 8 kW182 strings of 9 on 1 inverter8.01 kWp0.67
About 10 kW222 strings of 11 on 1 inverter9.79 kWp0.82