Qcells Q.TRON BLK M-G2H+ 430 with SolarEdge SE10000H-US
Compatibility and string sizing for this panel and solaredge inverter, calculated from both datasheets.
Compatible
Yes, with the SolarEdge S440 optimizer on every panel. Strings of 8–15 panels work (best 13), each delivering up to 5,700 W. One SolarEdge SE10000H-US takes up to 3 strings of 13: 36 panels, 15.48 kWp DC, DC/AC ratio 1.55.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- ✓ Module power430 W is within the S440 rating of 440 W.
- ✓ Max input voltageVoc at the record low is 42.3 V, within the 60 V optimizer limit.
- ✓ MPPT windowVmp stays inside 8–60 V from the coldest to the hottest day.
- ✓ Module short-circuit currentIsc 13.74 A is within the 15 A limit.
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 8–15 panels per string (best 13) |
| Chicago, IL | −21 °C | 8–15 panels per string (best 13) |
| Denver, CO | −23.6 °C | 8–15 panels per string (best 13) |
| Atlanta, GA | −9.5 °C | 8–15 panels per string (best 13) |
| Dallas, TX | −7.1 °C | 8–15 panels per string (best 13) |
| Phoenix, AZ | 1.3 °C | 8–15 panels per string (best 13) |
| Miami, FL | 5.9 °C | 8–15 panels per string (best 13) |
Common system sizes
How Qcells Q.TRON BLK M-G2H+ 430 panels lay out on the SolarEdge SE10000H-US for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | 14 | 1 string of 14 on 1 inverter | 6.02 kWp | 0.60 |
| About 8 kW | 19 | 1 × 10 + 1 × 9 panels on 1 inverter | 8.17 kWp | 0.82 |
| About 10 kW | 23 | 1 × 12 + 1 × 11 panels on 1 inverter | 9.89 kWp | 0.99 |