Home › Compatibility › Qcells Q.PEAK DUO XL-G11S.3/BFG 590 + APsystems DS3-S

Qcells Q.PEAK DUO XL-G11S.3/BFG 590 with APsystems DS3-S

Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.

!

Compatible, with a caution

Yes. Each DS3-S takes 2 panels, and up to 6 units fit on one 20 A branch circuit (12 panels). DC/AC ratio 1.84. Check the MPPT window, cold day; Module power pairing below.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 9.5%.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °CNot compatible: Max input voltage
Chicago, IL−21 °CNot compatible: Max input voltage
Denver, CO−23.6 °CNot compatible: Max input voltage
Atlanta, GA−9.5 °C2 panels per unit (check: MPPT window, cold day)
Dallas, TX−7.1 °C2 panels per unit (check: MPPT window, cold day)
Phoenix, AZ1.3 °C2 panels per unit (check: MPPT window, cold day)
Miami, FL5.9 °C2 panels per unit (check: MPPT window, cold day)

Common system sizes

How Qcells Q.PEAK DUO XL-G11S.3/BFG 590 panels lay out on the APsystems DS3-S for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW105 × DS3-S on 1 branch circuit5.90 kWp1.84
About 8 kW147 × DS3-S on 2 branch circuits8.26 kWp1.84
About 10 kW179 × DS3-S on 2 branch circuits10.03 kWp1.74