Qcells Q.PEAK DUO XL-G11S.3/BFG 590 with CPS (Chint Power) SCA25KTL-DO/US-208
Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.
Compatible
Yes. At a −10 °C record low and a 40 °C hot day, strings of 7–17 panels work. The longest string reaches 997 V on the coldest morning, under the 1000 V inverter limit. One CPS (Chint Power) SCA25KTL-DO/US-208 takes up to 3 strings of 17: 51 panels, 30.09 kWp DC, DC/AC ratio 1.20.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 9.5%.
- Voc on the coldest morning53.6 V × (1 + -0.27%/°C × (−10 − 25)) = 58.67 V per panel.
- Vmp on the hottest afternoonCells reach 67.5 °C (40 °C air plus the NMOT rise), so Vmp drops from 44.96 V to 37.70 V (Vmp coefficient taken as Pmax − Isc coefficient).
- Longest string1000 V inverter limit ÷ 58.67 V = 17 panels.
- Shortest string200 V MPPT minimum ÷ 37.70 V = 6 panels; start-up voltage needs 7.
- Strings per MPPTHot-day Isc 15.30 A per string, so the MPPT inputs take 2 + 2 + 2 string(s).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 7–16 panels per string (best 16) |
| Chicago, IL | −21 °C | 7–16 panels per string (best 16) |
| Denver, CO | −23.6 °C | 7–16 panels per string (best 16) |
| Atlanta, GA | −9.5 °C | 7–17 panels per string (best 17) |
| Dallas, TX | −7.1 °C | 7–17 panels per string (best 17) |
| Phoenix, AZ | 1.3 °C | 7–17 panels per string (best 17) |
| Miami, FL | 5.9 °C | 7–17 panels per string (best 17) |
Common system sizes
How Qcells Q.PEAK DUO XL-G11S.3/BFG 590 panels lay out on the CPS (Chint Power) SCA25KTL-DO/US-208 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| 1 inverter, fully loaded | 72 | 6 strings of 12 on 1 inverter | 42.48 kWp | 1.70 |
| 2 inverters, fully loaded | 144 | 12 strings of 12 on 2 inverters | 84.96 kWp | 1.70 |
| 4 inverters, fully loaded | 288 | 24 strings of 12 on 4 inverters | 169.92 kWp | 1.70 |