Qcells Q.TRON BLK M-G2+ 430 with Fronius Primo 10.0-1
Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.
Compatible
Yes. At a −10 °C record low and a 40 °C hot day, strings of 3–23 panels work. The longest string reaches 980 V on the coldest morning, under the 1000 V inverter limit. One Fronius Primo 10.0-1 takes up to 1 string of 21: 21 panels, 9.03 kWp DC, DC/AC ratio 0.90.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- Voc on the coldest morning39.32 V × (1 + -0.24%/°C × (−10 − 25)) = 42.62 V per panel.
- Vmp on the hottest afternoonCells reach 68.8 °C (40 °C air plus the NMOT rise), so Vmp drops from 32.94 V to 28.04 V (Vmp coefficient taken as Pmax − Isc coefficient).
- Longest string1000 V inverter limit ÷ 42.62 V = 23 panels.
- Shortest string80 V MPPT minimum ÷ 28.04 V = 3 panels; start-up voltage needs 3.
- Strings per MPPTHot-day Isc 13.98 A per string, so the MPPT inputs take 3 + 1 string(s); expect about 18.6% current clipping at peak.
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 3–22 panels per string (best 20) |
| Chicago, IL | −21 °C | 3–22 panels per string (best 21) |
| Denver, CO | −23.6 °C | 3–22 panels per string (best 20) |
| Atlanta, GA | −9.5 °C | 3–23 panels per string (best 21) |
| Dallas, TX | −7.1 °C | 3–23 panels per string (best 21) |
| Phoenix, AZ | 1.3 °C | 3–24 panels per string (best 22) |
| Miami, FL | 5.9 °C | 3–24 panels per string (best 22) |
Common system sizes
How Qcells Q.TRON BLK M-G2+ 430 panels lay out on the Fronius Primo 10.0-1 for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | 14 | 1 string of 14 on 1 inverter | 6.02 kWp | 0.60 |
| About 8 kW | 19 | 1 string of 19 on 1 inverter | 8.17 kWp | 0.82 |
| About 10 kW | 23 | 1 string of 23 on 1 inverter | 9.89 kWp | 0.99 |