Home › Compatibility › REC Alpha Pure-RX REC470AA + CPS (Chint Power) SCA50KTL-DO/US-480

REC Alpha Pure-RX REC470AA with CPS (Chint Power) SCA50KTL-DO/US-480

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 6–14 panels work. The longest string reaches 996 V on the coldest morning, under the 1000 V inverter limit. One CPS (Chint Power) SCA50KTL-DO/US-480 takes up to 13 strings of 14: 182 panels, 85.54 kWp DC, DC/AC ratio 1.71.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C6–13 panels per string (best 13)
Chicago, IL−21 °C6–13 panels per string (best 13)
Denver, CO−23.6 °C6–13 panels per string (best 13)
Atlanta, GA−9.5 °C6–14 panels per string (best 14)
Dallas, TX−7.1 °C6–14 panels per string (best 14)
Phoenix, AZ1.3 °C6–14 panels per string (best 14)
Miami, FL5.9 °C6–14 panels per string (best 14)

Common system sizes

How REC Alpha Pure-RX REC470AA panels lay out on the CPS (Chint Power) SCA50KTL-DO/US-480 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded18214 strings of 13 on 1 inverter85.54 kWp1.71
2 inverters, fully loaded36428 strings of 13 on 2 inverters171.08 kWp1.71
4 inverters, fully loaded72856 strings of 13 on 4 inverters342.16 kWp1.71