REC Alpha Pure-RX REC470AA with CPS (Chint Power) SCA50KTL-DO/US-480
Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.
Compatible
Yes. At a −10 °C record low and a 40 °C hot day, strings of 6–14 panels work. The longest string reaches 996 V on the coldest morning, under the 1000 V inverter limit. One CPS (Chint Power) SCA50KTL-DO/US-480 takes up to 13 strings of 14: 182 panels, 85.54 kWp DC, DC/AC ratio 1.71.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- Voc on the coldest morning65.6 V × (1 + -0.24%/°C × (−10 − 25)) = 71.11 V per panel.
- Vmp on the hottest afternoonCells reach 70.0 °C (40 °C air plus the NMOT rise), so Vmp drops from 55.4 V to 48.42 V (Vmp coefficient taken as Pmax − Isc coefficient).
- Longest string1000 V inverter limit ÷ 71.11 V = 14 panels.
- Shortest string200 V MPPT minimum ÷ 48.42 V = 5 panels; start-up voltage needs 6.
- Strings per MPPTHot-day Isc 9.11 A per string, so the MPPT inputs take 5 + 5 + 5 string(s).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 6–13 panels per string (best 13) |
| Chicago, IL | −21 °C | 6–13 panels per string (best 13) |
| Denver, CO | −23.6 °C | 6–13 panels per string (best 13) |
| Atlanta, GA | −9.5 °C | 6–14 panels per string (best 14) |
| Dallas, TX | −7.1 °C | 6–14 panels per string (best 14) |
| Phoenix, AZ | 1.3 °C | 6–14 panels per string (best 14) |
| Miami, FL | 5.9 °C | 6–14 panels per string (best 14) |
Common system sizes
How REC Alpha Pure-RX REC470AA panels lay out on the CPS (Chint Power) SCA50KTL-DO/US-480 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| 1 inverter, fully loaded | 182 | 14 strings of 13 on 1 inverter | 85.54 kWp | 1.71 |
| 2 inverters, fully loaded | 364 | 28 strings of 13 on 2 inverters | 171.08 kWp | 1.71 |
| 4 inverters, fully loaded | 728 | 56 strings of 13 on 4 inverters | 342.16 kWp | 1.71 |