REC Alpha Pure-RX REC470AA with Fronius Symo 24.0-3 480
Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.
Compatible
Yes. At a −10 °C record low and a 40 °C hot day, strings of 5–14 panels work. The longest string reaches 996 V on the coldest morning, under the 1000 V inverter limit. One Fronius Symo 24.0-3 480 takes up to 5 strings of 13: 65 panels, 30.55 kWp DC, DC/AC ratio 1.27.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- Voc on the coldest morning65.6 V × (1 + -0.24%/°C × (−10 − 25)) = 71.11 V per panel.
- Vmp on the hottest afternoonCells reach 70.0 °C (40 °C air plus the NMOT rise), so Vmp drops from 55.4 V to 48.42 V (Vmp coefficient taken as Pmax − Isc coefficient).
- Longest string1000 V inverter limit ÷ 71.11 V = 14 panels.
- Shortest string200 V MPPT minimum ÷ 48.42 V = 5 panels.
- Strings per MPPTHot-day Isc 9.11 A per string, so the MPPT inputs take 3 + 3 string(s); expect about 1.9% current clipping at peak.
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 5–13 panels per string (best 12) |
| Chicago, IL | −21 °C | 5–13 panels per string (best 12) |
| Denver, CO | −23.6 °C | 5–13 panels per string (best 12) |
| Atlanta, GA | −9.5 °C | 5–14 panels per string (best 13) |
| Dallas, TX | −7.1 °C | 5–14 panels per string (best 13) |
| Phoenix, AZ | 1.3 °C | 5–14 panels per string (best 13) |
| Miami, FL | 5.9 °C | 5–14 panels per string (best 13) |
Common system sizes
How REC Alpha Pure-RX REC470AA panels lay out on the Fronius Symo 24.0-3 480 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| 1 inverter, fully loaded | 65 | 5 strings of 13 on 1 inverter | 30.55 kWp | 1.27 |
| 2 inverters, fully loaded | 130 | 10 strings of 13 on 2 inverters | 61.10 kWp | 1.27 |
| 4 inverters, fully loaded | 260 | 20 strings of 13 on 4 inverters | 122.20 kWp | 1.27 |