Home › Compatibility › REC Alpha Pure-RX REC470AA + SMA SB3.8-1SP-US-40

REC Alpha Pure-RX REC470AA with SMA SB3.8-1SP-US-40

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 3–8 panels work. The longest string reaches 569 V on the coldest morning, under the 600 V inverter limit. One SMA SB3.8-1SP-US-40 takes up to 1 string of 8: 8 panels, 3.76 kWp DC, DC/AC ratio 0.99.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C3–8 panels per string (best 8)
Chicago, IL−21 °C3–8 panels per string (best 8)
Denver, CO−23.6 °C3–8 panels per string (best 8)
Atlanta, GA−9.5 °C3–8 panels per string (best 8)
Dallas, TX−7.1 °C3–8 panels per string (best 8)
Phoenix, AZ1.3 °C3–8 panels per string (best 8)
Miami, FL5.9 °C3–8 panels per string (best 8)

Common system sizes

How REC Alpha Pure-RX REC470AA panels lay out on the SMA SB3.8-1SP-US-40 for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW131 × 7 + 1 × 6 panels on 2 inverters6.11 kWp0.80
About 8 kW171 × 5 + 3 × 4 panels on 2 inverters7.99 kWp1.05
About 10 kW213 strings of 7 on 3 inverters9.87 kWp0.87