Home › Compatibility › REC Alpha Pure-RX REC470AA + Solis S6-GC50K-US

REC Alpha Pure-RX REC470AA with Solis S6-GC50K-US

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 4–14 panels work. The longest string reaches 996 V on the coldest morning, under the 1000 V inverter limit. One Solis S6-GC50K-US takes up to 8 strings of 14: 112 panels, 52.64 kWp DC, DC/AC ratio 1.05.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C4–13 panels per string (best 13)
Chicago, IL−21 °C4–13 panels per string (best 13)
Denver, CO−23.6 °C4–13 panels per string (best 13)
Atlanta, GA−9.5 °C4–14 panels per string (best 14)
Dallas, TX−7.1 °C4–14 panels per string (best 14)
Phoenix, AZ1.3 °C4–14 panels per string (best 14)
Miami, FL5.9 °C4–14 panels per string (best 14)

Common system sizes

How REC Alpha Pure-RX REC470AA panels lay out on the Solis S6-GC50K-US for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded1128 strings of 14 on 1 inverter52.64 kWp1.05
2 inverters, fully loaded22416 strings of 14 on 2 inverters105.28 kWp1.05
4 inverters, fully loaded44832 strings of 14 on 4 inverters210.56 kWp1.05