Home › Compatibility › Silfab SIL-410HC+ + Enphase IQ8HC-72-M-US
Silfab SIL-410HC+ with Enphase IQ8HC-72-M-US
Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.
✓
Compatible
Yes. Each IQ8HC-72-M-US takes 1 panel, and up to 10 units fit on one 20 A branch circuit (10 panels). DC/AC ratio 1.08.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- ✓ Max input voltageVoc at the record low is 50.4 V, within the 60 V limit (84%).
- ✓ MPPT window, hot dayVmp on the hottest day is 30.9 V, inside 29.5–45 V.
- ✓ MPPT window, cold dayVmp on the coldest day is 44.9 V, inside the MPPT range.
- ✓ Start-up voltageHot-day Voc 39.0 V clears the 22 V start-up voltage.
- ✓ Module short-circuit currentIsc 11.15 A is within the 20 A max module Isc.
- ✓ Module power pairing410 W is inside the recommended 320–540 (DC/AC 1.08).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 1 panel per unit (check: MPPT window, cold day) |
| Chicago, IL | −21 °C | 1 panel per unit (check: MPPT window, cold day) |
| Denver, CO | −23.6 °C | 1 panel per unit (check: MPPT window, cold day) |
| Atlanta, GA | −9.5 °C | 1 panel per unit |
| Dallas, TX | −7.1 °C | 1 panel per unit |
| Phoenix, AZ | 1.3 °C | 1 panel per unit |
| Miami, FL | 5.9 °C | 1 panel per unit |
Common system sizes
How Silfab SIL-410HC+ panels lay out on the Enphase IQ8HC-72-M-US for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | 15 | 15 × IQ8HC-72-M-US on 2 branch circuits | 6.15 kWp | 1.08 |
| About 8 kW | 20 | 20 × IQ8HC-72-M-US on 2 branch circuits | 8.20 kWp | 1.08 |
| About 10 kW | 24 | 24 × IQ8HC-72-M-US on 3 branch circuits | 9.84 kWp | 1.08 |