Home › Compatibility › Silfab SIL-420HU + APsystems DS3-L
Silfab SIL-420HU with APsystems DS3-L
Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.
✓
Compatible
Yes. Each DS3-L takes 2 panels, and up to 5 units fit on one 20 A branch circuit (10 panels). DC/AC ratio 1.09.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- ✓ Max input voltageVoc at the record low is 53.7 V, within the 60 V limit (89%).
- ✓ MPPT window, hot dayVmp on the hottest day is 34.8 V, inside 25–55 V.
- ✓ MPPT window, cold dayVmp on the coldest day is 46.3 V, inside the MPPT range.
- ✓ Input currentImp 10.17 A is within the 18 A max input current. The datasheet gives no separate Isc limit.
- ✓ Module power pairing420 W is inside the recommended 265–570 (DC/AC 1.09).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 2 panels per unit |
| Chicago, IL | −21 °C | 2 panels per unit |
| Denver, CO | −23.6 °C | 2 panels per unit |
| Atlanta, GA | −9.5 °C | 2 panels per unit |
| Dallas, TX | −7.1 °C | 2 panels per unit |
| Phoenix, AZ | 1.3 °C | 2 panels per unit |
| Miami, FL | 5.9 °C | 2 panels per unit |
Common system sizes
How Silfab SIL-420HU panels lay out on the APsystems DS3-L for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | 14 | 7 × DS3-L on 2 branch circuits | 5.88 kWp | 1.09 |
| About 8 kW | 19 | 10 × DS3-L on 2 branch circuits | 7.98 kWp | 1.04 |
| About 10 kW | 24 | 12 × DS3-L on 3 branch circuits | 10.08 kWp | 1.09 |