Home › Compatibility › SunPower SPR-MAX3-425-R + EG4 FlexBOSS21

SunPower SPR-MAX3-425-R with EG4 FlexBOSS21

Compatibility and string sizing for this panel and hybrid inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 6–13 panels work. The longest string reaches 572 V on the coldest morning, under the 600 V inverter limit. One EG4 FlexBOSS21 takes up to 4 strings of 11: 44 panels, 18.70 kWp DC, DC/AC ratio 1.17.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C6–13 panels per string (best 10)
Chicago, IL−21 °C6–13 panels per string (best 10)
Denver, CO−23.6 °C6–13 panels per string (best 10)
Atlanta, GA−9.5 °C6–13 panels per string (best 11)
Dallas, TX−7.1 °C6–13 panels per string (best 11)
Phoenix, AZ1.3 °C6–13 panels per string (best 11)
Miami, FL5.9 °C6–14 panels per string (best 11)

Common system sizes

How SunPower SPR-MAX3-425-R panels lay out on the EG4 FlexBOSS21 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded484 strings of 12 on 1 inverter20.40 kWp1.27
2 inverters, fully loaded968 strings of 12 on 2 inverters40.80 kWp1.27
4 inverters, fully loaded19216 strings of 12 on 4 inverters81.60 kWp1.27