Home › Compatibility › Talesun BiPro TM7G54M-425 + CPS (Chint Power) SCA60KTL-DO/US-480

Talesun BiPro TM7G54M-425 with CPS (Chint Power) SCA60KTL-DO/US-480

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 10–24 panels work. The longest string reaches 1,000 V on the coldest morning, under the 1000 V inverter limit. One CPS (Chint Power) SCA60KTL-DO/US-480 takes up to 8 strings of 24: 192 panels, 81.60 kWp DC, DC/AC ratio 1.36.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C10–23 panels per string (best 23)
Chicago, IL−21 °C10–23 panels per string (best 23)
Denver, CO−23.6 °C10–23 panels per string (best 23)
Atlanta, GA−9.5 °C10–24 panels per string (best 24)
Dallas, TX−7.1 °C10–24 panels per string (best 24)
Phoenix, AZ1.3 °C10–24 panels per string (best 24)
Miami, FL5.9 °C10–24 panels per string (best 24)

Common system sizes

How Talesun BiPro TM7G54M-425 panels lay out on the CPS (Chint Power) SCA60KTL-DO/US-480 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded2079 strings of 23 on 1 inverter87.97 kWp1.47
2 inverters, fully loaded41418 strings of 23 on 2 inverters175.95 kWp1.47
4 inverters, fully loaded82836 strings of 23 on 4 inverters351.90 kWp1.47