Talesun BiPro TM7G54M-425 with CPS (Chint Power) SCA60KTL-DO/US-480
Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.
Compatible
Yes. At a −10 °C record low and a 40 °C hot day, strings of 10–24 panels work. The longest string reaches 1,000 V on the coldest morning, under the 1000 V inverter limit. One CPS (Chint Power) SCA60KTL-DO/US-480 takes up to 8 strings of 24: 192 panels, 81.60 kWp DC, DC/AC ratio 1.36.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.
- Voc on the coldest morning38.3 V × (1 + -0.25%/°C × (−10 − 25)) = 41.65 V per panel.
- Vmp on the hottest afternoonCells reach 71.2 °C (40 °C air plus the NMOT rise), so Vmp drops from 31.7 V to 26.63 V (Vmp coefficient taken as Pmax − Isc coefficient).
- Longest string1000 V inverter limit ÷ 41.65 V = 24 panels.
- Shortest string200 V MPPT minimum ÷ 26.63 V = 8 panels; start-up voltage needs 10.
- Strings per MPPTHot-day Isc 15.90 A per string, so the MPPT inputs take 3 + 3 + 3 string(s).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 10–23 panels per string (best 23) |
| Chicago, IL | −21 °C | 10–23 panels per string (best 23) |
| Denver, CO | −23.6 °C | 10–23 panels per string (best 23) |
| Atlanta, GA | −9.5 °C | 10–24 panels per string (best 24) |
| Dallas, TX | −7.1 °C | 10–24 panels per string (best 24) |
| Phoenix, AZ | 1.3 °C | 10–24 panels per string (best 24) |
| Miami, FL | 5.9 °C | 10–24 panels per string (best 24) |
Common system sizes
How Talesun BiPro TM7G54M-425 panels lay out on the CPS (Chint Power) SCA60KTL-DO/US-480 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| 1 inverter, fully loaded | 207 | 9 strings of 23 on 1 inverter | 87.97 kWp | 1.47 |
| 2 inverters, fully loaded | 414 | 18 strings of 23 on 2 inverters | 175.95 kWp | 1.47 |
| 4 inverters, fully loaded | 828 | 36 strings of 23 on 4 inverters | 351.90 kWp | 1.47 |