Home › Compatibility › Talesun BiPro TM7G54M-425 + Hoymiles HMS-800-2T-NA

Talesun BiPro TM7G54M-425 with Hoymiles HMS-800-2T-NA

Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.

!

Compatible, with a caution

Yes. Each HMS-800-2T-NA takes 2 panels, and up to 5 units fit on one 20 A branch circuit (10 panels). DC/AC ratio 1.18. Check the Input current below.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C2 panels per unit (check: Input current)
Chicago, IL−21 °C2 panels per unit (check: Input current)
Denver, CO−23.6 °C2 panels per unit (check: Input current)
Atlanta, GA−9.5 °C2 panels per unit (check: Input current)
Dallas, TX−7.1 °C2 panels per unit (check: Input current)
Phoenix, AZ1.3 °C2 panels per unit (check: Input current)
Miami, FL5.9 °C2 panels per unit (check: Input current)

Common system sizes

How Talesun BiPro TM7G54M-425 panels lay out on the Hoymiles HMS-800-2T-NA for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW147 × HMS-800-2T-NA on 2 branch circuits5.95 kWp1.18
About 8 kW1910 × HMS-800-2T-NA on 2 branch circuits8.07 kWp1.12
About 10 kW2412 × HMS-800-2T-NA on 3 branch circuits10.20 kWp1.18