Home › Compatibility › Talesun BiPro TM7G72M-585 + SMA STP 33-US-41

Talesun BiPro TM7G72M-585 with SMA STP 33-US-41

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 5–17 panels work. The longest string reaches 961 V on the coldest morning, under the 1000 V inverter limit. One SMA STP 33-US-41 takes up to 5 strings of 17: 85 panels, 49.73 kWp DC, DC/AC ratio 1.49.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C5–17 panels per string (best 17)
Chicago, IL−21 °C5–17 panels per string (best 17)
Denver, CO−23.6 °C5–17 panels per string (best 17)
Atlanta, GA−9.5 °C5–17 panels per string (best 17)
Dallas, TX−7.1 °C5–17 panels per string (best 17)
Phoenix, AZ1.3 °C5–18 panels per string (best 18)
Miami, FL5.9 °C5–18 panels per string (best 18)

Common system sizes

How Talesun BiPro TM7G72M-585 panels lay out on the SMA STP 33-US-41 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded855 strings of 17 on 1 inverter49.73 kWp1.49
2 inverters, fully loaded17010 strings of 17 on 2 inverters99.45 kWp1.49
4 inverters, fully loaded34020 strings of 17 on 4 inverters198.90 kWp1.49