Home › Compatibility › Trina Solar TSM-425NE09RC05 + Enphase IQ8H-240-72-2-US

Trina Solar TSM-425NE09RC05 with Enphase IQ8H-240-72-2-US

Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.

!

Compatible, with a caution

Yes. Each IQ8H-240-72-2-US takes 1 panel, and up to 10 units fit on one 20 A branch circuit (10 panels). DC/AC ratio 1.12. Check the MPPT window, cold day below.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C1 panel per unit (check: MPPT window, cold day)
Chicago, IL−21 °C1 panel per unit (check: MPPT window, cold day)
Denver, CO−23.6 °C1 panel per unit (check: MPPT window, cold day)
Atlanta, GA−9.5 °C1 panel per unit (check: MPPT window, cold day)
Dallas, TX−7.1 °C1 panel per unit (check: MPPT window, cold day)
Phoenix, AZ1.3 °C1 panel per unit (check: MPPT window, cold day)
Miami, FL5.9 °C1 panel per unit (check: MPPT window, cold day)

Common system sizes

How Trina Solar TSM-425NE09RC05 panels lay out on the Enphase IQ8H-240-72-2-US for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW1414 × IQ8H-240-72-2-US on 2 branch circuits5.95 kWp1.12
About 8 kW1919 × IQ8H-240-72-2-US on 2 branch circuits8.07 kWp1.12
About 10 kW2424 × IQ8H-240-72-2-US on 3 branch circuits10.20 kWp1.12