Home › Compatibility › Trina Solar TSM-425NE09RC05 + Enphase IQ8MC-72-M-US
Trina Solar TSM-425NE09RC05 with Enphase IQ8MC-72-M-US
Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.
!
Compatible, with a caution
Yes. Each IQ8MC-72-M-US takes 1 panel, and up to 12 units fit on one 20 A branch circuit (12 panels). DC/AC ratio 1.33. Check the MPPT window, cold day below.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- ✓ Max input voltageVoc at the record low is 55.9 V, within the 60 V limit (93%).
- ✓ MPPT window, hot dayVmp on the hottest day is 36.0 V, inside 25–45 V.
- ! MPPT window, cold dayVmp rises to 48.7 V on cold days, above the 45 V MPPT maximum, so tracking is off-peak then.
- ✓ Start-up voltageHot-day Voc 45.5 V clears the 22 V start-up voltage.
- ✓ Module short-circuit currentIsc 10.47 A is within the 20 A max module Isc.
- ✓ Module power pairing425 W is inside the recommended 260–460 (DC/AC 1.33).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 1 panel per unit (check: MPPT window, cold day) |
| Chicago, IL | −21 °C | 1 panel per unit (check: MPPT window, cold day) |
| Denver, CO | −23.6 °C | 1 panel per unit (check: MPPT window, cold day) |
| Atlanta, GA | −9.5 °C | 1 panel per unit (check: MPPT window, cold day) |
| Dallas, TX | −7.1 °C | 1 panel per unit (check: MPPT window, cold day) |
| Phoenix, AZ | 1.3 °C | 1 panel per unit (check: MPPT window, cold day) |
| Miami, FL | 5.9 °C | 1 panel per unit (check: MPPT window, cold day) |
Common system sizes
How Trina Solar TSM-425NE09RC05 panels lay out on the Enphase IQ8MC-72-M-US for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | 14 | 14 × IQ8MC-72-M-US on 2 branch circuits | 5.95 kWp | 1.33 |
| About 8 kW | 19 | 19 × IQ8MC-72-M-US on 2 branch circuits | 8.07 kWp | 1.33 |
| About 10 kW | 24 | 24 × IQ8MC-72-M-US on 2 branch circuits | 10.20 kWp | 1.33 |