Home › Compatibility › Trina Solar TSM-435NE09RH05 + SMA SB6.0-1SP-US-41

Trina Solar TSM-435NE09RH05 with SMA SB6.0-1SP-US-41

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 5–16 panels work. The longest string reaches 598 V on the coldest morning, under the 600 V inverter limit. One SMA SB6.0-1SP-US-41 takes up to 1 string of 16: 16 panels, 6.96 kWp DC, DC/AC ratio 1.16.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C5–15 panels per string (best 15)
Chicago, IL−21 °C5–15 panels per string (best 15)
Denver, CO−23.6 °C5–15 panels per string (best 15)
Atlanta, GA−9.5 °C5–16 panels per string (best 16)
Dallas, TX−7.1 °C5–16 panels per string (best 16)
Phoenix, AZ1.3 °C5–16 panels per string (best 16)
Miami, FL5.9 °C5–16 panels per string (best 16)

Common system sizes

How Trina Solar TSM-435NE09RH05 panels lay out on the SMA SB6.0-1SP-US-41 for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW141 string of 14 on 1 inverter6.09 kWp1.01
About 8 kW182 strings of 9 on 1 inverter7.83 kWp1.30
About 10 kW231 × 12 + 1 × 11 panels on 2 inverters10.01 kWp0.83