Home › Compatibility › Trina Solar Vertex S+ TSM-440NEG9R.28 + CPS (Chint Power) SCA60KTL-DO/US-480

Trina Solar Vertex S+ TSM-440NEG9R.28 with CPS (Chint Power) SCA60KTL-DO/US-480

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 8–17 panels work. The longest string reaches 962 V on the coldest morning, under the 1000 V inverter limit. One CPS (Chint Power) SCA60KTL-DO/US-480 takes up to 12 strings of 17: 204 panels, 89.76 kWp DC, DC/AC ratio 1.50.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C8–17 panels per string (best 17)
Chicago, IL−21 °C8–17 panels per string (best 17)
Denver, CO−23.6 °C8–17 panels per string (best 17)
Atlanta, GA−9.5 °C8–17 panels per string (best 17)
Dallas, TX−7.1 °C8–17 panels per string (best 17)
Phoenix, AZ1.3 °C8–18 panels per string (best 18)
Miami, FL5.9 °C8–18 panels per string (best 18)

Common system sizes

How Trina Solar Vertex S+ TSM-440NEG9R.28 panels lay out on the CPS (Chint Power) SCA60KTL-DO/US-480 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded20412 strings of 17 on 1 inverter89.76 kWp1.50
2 inverters, fully loaded40824 strings of 17 on 2 inverters179.52 kWp1.50
4 inverters, fully loaded81648 strings of 17 on 4 inverters359.04 kWp1.50