Home › Compatibility › Trina Solar Vertex S+ TSM-440NEG9R.28 + Hoymiles HMS-500-1T-NA
Trina Solar Vertex S+ TSM-440NEG9R.28 with Hoymiles HMS-500-1T-NA
Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.
✓
Compatible
Yes. Each HMS-500-1T-NA takes 1 panel, and up to 8 units fit on one 20 A branch circuit (8 panels). DC/AC ratio 0.93.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- ✓ Max input voltageVoc at the record low is 56.6 V, within the 65 V limit (87%).
- ✓ MPPT window, hot dayVmp on the hottest day is 37.4 V, inside 16–60 V.
- ✓ MPPT window, cold dayVmp on the coldest day is 49.1 V, inside the MPPT range.
- ✓ Start-up voltageHot-day Voc 46.7 V clears the 22 V start-up voltage.
- ✓ Input currentImp 10.02 A is within the 16 A max input current. The datasheet gives no separate Isc limit.
- ✓ Module power pairing440 W is inside the recommended 400–670 (DC/AC 0.93).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 1 panel per unit |
| Chicago, IL | −21 °C | 1 panel per unit |
| Denver, CO | −23.6 °C | 1 panel per unit |
| Atlanta, GA | −9.5 °C | 1 panel per unit |
| Dallas, TX | −7.1 °C | 1 panel per unit |
| Phoenix, AZ | 1.3 °C | 1 panel per unit |
| Miami, FL | 5.9 °C | 1 panel per unit |
Common system sizes
How Trina Solar Vertex S+ TSM-440NEG9R.28 panels lay out on the Hoymiles HMS-500-1T-NA for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | 14 | 14 × HMS-500-1T-NA on 2 branch circuits | 6.16 kWp | 0.93 |
| About 8 kW | 18 | 18 × HMS-500-1T-NA on 3 branch circuits | 7.92 kWp | 0.93 |
| About 10 kW | 23 | 23 × HMS-500-1T-NA on 3 branch circuits | 10.12 kWp | 0.93 |