Trina Solar Vertex S+ TSM-440NEG9R.28 with Solis S5-GC125K-US
Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.
Compatible
Yes. At a −10 °C record low and a 40 °C hot day, strings of 5–17 panels work. The longest string reaches 962 V on the coldest morning, under the 1000 V inverter limit. One Solis S5-GC125K-US takes up to 20 strings of 17: 340 panels, 149.60 kWp DC, DC/AC ratio 1.20.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- Voc on the coldest morning52.2 V × (1 + -0.24%/°C × (−10 − 25)) = 56.58 V per panel.
- Vmp on the hottest afternoonCells reach 68.8 °C (40 °C air plus the NMOT rise), so Vmp drops from 43.9 V to 37.37 V (Vmp coefficient taken as Pmax − Isc coefficient).
- Longest string1000 V inverter limit ÷ 56.58 V = 17 panels.
- Shortest string180 V MPPT minimum ÷ 37.37 V = 5 panels; start-up voltage needs 5.
- Strings per MPPTHot-day Isc 10.87 A per string, so the MPPT inputs take 2 + 2 + 2 + 2 + 2 + 2 + 2 + 2 + 2 + 2 string(s).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 5–17 panels per string (best 17) |
| Chicago, IL | −21 °C | 5–17 panels per string (best 17) |
| Denver, CO | −23.6 °C | 5–17 panels per string (best 17) |
| Atlanta, GA | −9.5 °C | 5–17 panels per string (best 17) |
| Dallas, TX | −7.1 °C | 5–17 panels per string (best 17) |
| Phoenix, AZ | 1.3 °C | 5–18 panels per string (best 18) |
| Miami, FL | 5.9 °C | 5–18 panels per string (best 18) |
Common system sizes
How Trina Solar Vertex S+ TSM-440NEG9R.28 panels lay out on the Solis S5-GC125K-US for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| 1 inverter, fully loaded | 340 | 20 strings of 17 on 1 inverter | 149.60 kWp | 1.20 |
| 2 inverters, fully loaded | 680 | 40 strings of 17 on 2 inverters | 299.20 kWp | 1.20 |
| 4 inverters, fully loaded | 1360 | 80 strings of 17 on 4 inverters | 598.40 kWp | 1.20 |