Home › Calculators › Panel load

Electrical panel load calculator

Adding an EV charger, a heat pump or a battery? Check whether your existing service can take it, with the NEC 220.83 method for existing homes or 220.87 using your utility's 12-month demand data.

Existing appliancesNameplate (VA)
Loads you are addingVA

How it works

NEC 220.83 (existing dwelling): add up general lighting and receptacles at 3 VA per square foot, 1,500 VA for each kitchen small-appliance and laundry circuit, and the nameplate rating of every fastened-in-place appliance, range, dryer and water heater, plus the new loads. The first 8 kVA counts at 100% and the rest at 40%. When new heating or cooling is installed, such as a heat pump, it is added at 100% outside that formula (220.83(B)), and the old equipment it replaces is left out. Existing heating and cooling count once, the larger of the two (220.60).

NEC 220.87 (measured demand): take the highest demand from a full year of utility data (15-minute intervals), multiply by 125%, and add the new load at 100%. Many utilities show this in the online account or provide it on request.

An EV charger counts at its nameplate rating or 7,200 W, whichever is larger (220.57). The result in amps is the load ÷ 240 V, compared with the service rating. If it doesn't fit, a load management system (220.70, 750.30) can keep the total under the limit instead of a service upgrade.

Questions

Can a 100 A panel handle an EV charger?

Often, at a lower charging current. A 2,000 sq ft home with gas heat and an electric dryer and range can calculate to 80–95 A before the charger, so a 7.2 kW charger usually pushes it over. A 16–24 A setting or a load manager often makes it work.

Does adding solar panels count as load?

No. Solar is a source, not a load. Whether the solar breaker fits is a separate busbar check, the 120% rule in NEC 705.12.

Estimates only, based on NEC 2020/2023 tables. Check the code edition your jurisdiction uses, the equipment datasheets and your AHJ before you build.