Solar fuse size calculator

Find out whether strings in parallel need fuses, which fuse size to use and how big the combined output overcurrent device has to be.

How it works

A string needs overcurrent protection when the other strings in parallel can push more current into it during a fault than the module's maximum series fuse rating (NEC 690.9(A)). With one or two strings that can't happen. With three or more it usually can.

The fuse must be at least 125% of the maximum circuit current, which is Isc × 1.25 × 1.25 = 1.56 × Isc, rounded up to a standard size, and no larger than the module's series fuse rating (690.9(B)).

The combined output circuit carries all strings: Isc × 1.25 × the number of strings, and its overcurrent device follows the same 125% rule.

Questions

Do I need fuses for two strings in parallel?

No. With two strings, the most current one string can receive in a fault is the other string’s current, which is below the module’s series fuse rating.

Why is the fuse size 1.56 × Isc?

Isc × 1.25 for high irradiance (690.8(A)), then × 1.25 again because the overcurrent device must be rated for 125% of continuous current (690.9(B)).

Estimates only, based on NEC 2020/2023 tables. Check the code edition your jurisdiction uses, the equipment datasheets and your AHJ before you build.