How it works
For a PV string, the maximum circuit current is the module short-circuit current × 1.25 (NEC 690.8(A)), multiplied by the number of strings in parallel. The conductor then has to pass two checks (690.8(B)):
- Terminals: 125% of that current must not exceed the conductor's ampacity in the 75 °C column of Table 310.16 (60 °C for equipment that is only rated for 60 °C).
- Conditions of use: the 90 °C ampacity, multiplied by the temperature correction and the conduit fill adjustment, must not be less than the maximum current.
Temperature correction uses the 310.15(B) equation √((90 − ambient) ÷ 60). Raceways on a roof less than 7/8 in above it add 33 °C (310.15(B)(2)). More than three current-carrying conductors in a raceway reduce ampacity by 310.15(C)(1): 80% for 4–6, 70% for 7–9, 50% for 10–20.
The overcurrent device has to be at least 125% of the maximum current, rounded up to a standard size (240.6(A)), and the conductor must be protected by it, including the small-conductor limits of 240.4(D): 15 A on 14 AWG, 20 A on 12 AWG and 30 A on 10 AWG copper.
Voltage drop uses the operating current (Imp for DC) and the DC resistance at 75 °C from Chapter 9 Table 8: 2 × length × current × resistance per foot. For inverter AC output, enter the inverter's maximum continuous output current from its datasheet; the same 125% rules apply (705.28).