Home › Calculators › Wire size

Solar wire size calculator

Find the smallest conductor for a PV string, a combined DC circuit or an inverter AC output. It checks ampacity at the terminals and under your conditions, the overcurrent device, and voltage drop.

How it works

For a PV string, the maximum circuit current is the module short-circuit current × 1.25 (NEC 690.8(A)), multiplied by the number of strings in parallel. The conductor then has to pass two checks (690.8(B)):

  1. Terminals: 125% of that current must not exceed the conductor's ampacity in the 75 °C column of Table 310.16 (60 °C for equipment that is only rated for 60 °C).
  2. Conditions of use: the 90 °C ampacity, multiplied by the temperature correction and the conduit fill adjustment, must not be less than the maximum current.

Temperature correction uses the 310.15(B) equation √((90 − ambient) ÷ 60). Raceways on a roof less than 7/8 in above it add 33 °C (310.15(B)(2)). More than three current-carrying conductors in a raceway reduce ampacity by 310.15(C)(1): 80% for 4–6, 70% for 7–9, 50% for 10–20.

The overcurrent device has to be at least 125% of the maximum current, rounded up to a standard size (240.6(A)), and the conductor must be protected by it, including the small-conductor limits of 240.4(D): 15 A on 14 AWG, 20 A on 12 AWG and 30 A on 10 AWG copper.

Voltage drop uses the operating current (Imp for DC) and the DC resistance at 75 °C from Chapter 9 Table 8: 2 × length × current × resistance per foot. For inverter AC output, enter the inverter's maximum continuous output current from its datasheet; the same 125% rules apply (705.28).

Questions

What size wire do I need for a solar panel string?

Most residential strings with 13–15 A modules use 10 AWG copper PV wire. It covers Isc × 1.56 at the terminals and holds up in hot rooftop conduit, as long as the run is short enough to keep voltage drop near 1–2%.

Why multiply Isc by 1.25 twice?

The first 1.25 (690.8(A)) covers irradiance above the 1,000 W/m² test condition. The second 1.25 treats the circuit as continuous duty for the terminal check and the overcurrent device. Together they make 1.56 × Isc.

How much voltage drop is acceptable for solar?

The NEC has no mandatory limit for PV circuits. Most designers aim for 1–2% on DC and 1–2% on AC, around 3% total, because every percent of drop is lost energy.

Estimates only, based on NEC 2020/2023 tables. Check the code edition your jurisdiction uses, the equipment datasheets and your AHJ before you build.